Ibalwa njani impumelelo ye-transformer kwimilinganiselo yelahleko

 May 19, 2026

 Shiya umyalezo

 

Q: Kunikwe i-P₀ kunye ne-Pₖ kwiimvavanyo, ndibala njani ukusebenza kakuhle kumanqanaba omthwalo ahlukeneyo?

 

A: Ukusebenza kakuhle η=P_out / (P_out + P₀ + ² × Pₖ) × 100%, apho=umba womthwalo.

Umzekelo: 10 MVA isiguquli, P₀=12 kW, Pₖ=85 kW:

Layisha

Imveliso (kW)

P₀ (kW)

²×Pₖ (kW)

η (%)

25%

0.25

2,500

12

5.3

99.31

50%

0.50

5,000

12

21.3

99.34

75%

0.75

7,500

12

47.8

99.21

100%

1.00

10,000

12

85.0

99.04

120%

1.20

12,000

12

122.4

98.89

Obona buchule buphezulu kwi=√(P₀ / Pₖ)=0.376 → ~ 37.6% umthwalo.

Imigangatho yokusebenza kakuhle kwamandla:

• IEC 60076-20: Iiklasi zeEEI A (ezona ziphezulu) → D.

• I-EU Ecodesign 2019/1783: Inqanaba lesi-2 (2021), iNqanaba lesi-3 (2025–27).

• I-DOE 10 CFR iSigaba 431: umthetho omtsha osebenza ngoJuni 2026.

• GB 20052-2020 (eTshayina): IBanga loku-1 (elona liphezulu) → 3.

• IS 1180 (India): BEE Star Rating 1–5.

Indlela ye-TCO: TCO=Ixabiso + A × P₀ + B × Pₖ

A ≈ $3,000–8,000/kW (akukho{4}}umthwalo weendleko ezinkulu).

B ≈ $ 500-2,000 / kW (umthwalo weendleko ezinkulu).

Thumela u kuphanda
Thumela u kuphanda