Q: Kunikwe i-P₀ kunye ne-Pₖ kwiimvavanyo, ndibala njani ukusebenza kakuhle kumanqanaba omthwalo ahlukeneyo?
A: Ukusebenza kakuhle η=P_out / (P_out + P₀ + ² × Pₖ) × 100%, apho=umba womthwalo.
Umzekelo: 10 MVA isiguquli, P₀=12 kW, Pₖ=85 kW:
|
Layisha |
|
Imveliso (kW) |
P₀ (kW) |
²×Pₖ (kW) |
η (%) |
|
25% |
0.25 |
2,500 |
12 |
5.3 |
99.31 |
|
50% |
0.50 |
5,000 |
12 |
21.3 |
99.34 |
|
75% |
0.75 |
7,500 |
12 |
47.8 |
99.21 |
|
100% |
1.00 |
10,000 |
12 |
85.0 |
99.04 |
|
120% |
1.20 |
12,000 |
12 |
122.4 |
98.89 |
Obona buchule buphezulu kwi=√(P₀ / Pₖ)=0.376 → ~ 37.6% umthwalo.
Imigangatho yokusebenza kakuhle kwamandla:
• IEC 60076-20: Iiklasi zeEEI A (ezona ziphezulu) → D.
• I-EU Ecodesign 2019/1783: Inqanaba lesi-2 (2021), iNqanaba lesi-3 (2025–27).
• I-DOE 10 CFR iSigaba 431: umthetho omtsha osebenza ngoJuni 2026.
• GB 20052-2020 (eTshayina): IBanga loku-1 (elona liphezulu) → 3.
• IS 1180 (India): BEE Star Rating 1–5.
Indlela ye-TCO: TCO=Ixabiso + A × P₀ + B × Pₖ
A ≈ $3,000–8,000/kW (akukho{4}}umthwalo weendleko ezinkulu).
B ≈ $ 500-2,000 / kW (umthwalo weendleko ezinkulu).