Q: Kufuneka ndivavanye intambo eyi-220 kV, ubude obuyi-8 km. Loluphi ukalisho lwe-SR endiludingayo?

 

A: Inkqubo yokulinganisa inamanyathelo asi-7: misela iimfuno zovavanyo → bala C → qikelela L → bala ii-f_res → qinisekisa amanqaku → phinda-phinda → gqibezela.

Inyathelo-nge{1}}inyathelo - 220 intambo ye-kV, 8 km:

1. IEC 60840: V_Uvavanyo=2.0 × 127 kV=254 kV. Ubude bexesha le-60 min.

2. C ≈ 8 km × 0.2 μF/km=1.6 μF.

3. Cinga nge-3× 100 kV/2 A ii-reactors ngokunxuseneyo: L=26.7 H, f=24.4 Hz.

4. Okwangoku ku-254 kV: I=V × 2πf × C=6.9 A. Kodwa 3×2A → 6A iyonke → AYILUNGILE.

5. Nyukela kwi-3× 100 kV/4 A reactors: iyonke I=12 A → Kulungile. P_ku=254×6.9/35=50 kW.

6. Ubunzima bubonke: 3×450 kg + 200 + 150 + 100=~1,800 kg.

 

Ubungakanani besishwankathelo seemeko eziqhelekileyo:

Imeko

V_Vavanyo (kV)

C (μF)

f (Hz)

Inkqubo eCetyisiweyo

33 kV intambo, 3 km

48

0.6

45

60 kV/2A × 1, 5 kW

Intambo ye-110 kV, 5 km

160

1.0

24

200 kV/4A ×2, 20 kW

Intambo ye-220 kV, 8 km

254

1.6

24

300 kV/4A × 3, 50 kW

Intambo ye-400 kV, 5 km

330

1.0

48

400 kV/2A ×2, 25 kW

GIS 245 kV, 10 bays

230

0.05

80

300 kV/1A ×2, 5 kW

Ijenereyitha 100 MVA

28

2.5

45

30 kV/5A, 10 kW

 

Izikhumbuzo ezibalulekileyo:

• +20% umda kumlinganiselo wombane wereactor{1}}% umda ngokomlinganiselo wangoku.

• Ukuba i-P_in > 100 kW, qwalasela uvavanyo lwamacandelo (okuvunyelwa yimigangatho emininzi).

• Oyena Q unokuba ngaphantsi kunoqikelelo - lwesicwangciso esilondolozayo sithintela ukusilela ebaleni.

Thumela u kuphanda