Uyifunda njani kwaye uyiqonde njani i-Nameplate yangoku yeTransformer (CT)?
I-Current Transformer (CT) yehla i-high current (inqanaba le-kA) kwixabiso elincinci, elinokulinganiswa (1 A okanye 5 A). Oku kuvumela uxhulumaniso olukhuselekileyo kwiimitha, iilayidi, kunye nezixhobo zokukhusela. Ii-transformers zangoku (CTs) zizinto ezibalulekileyo kwiinkqubo zombane zokulinganisa nokubeka iliso ukuhamba kwangoku. Ukuqonda indlela yokufunda nokutolika ulwazi kwi-nameplate ye-CT kubalulekile ekuqinisekiseni ukufakela nokusebenza ngokufanelekileyo kwesixhobo. Ukufunda i-nameplate ye-CT ngokuchanekileyo kuqinisekisa ukulinganisa okuchanekileyo, ukukhuselwa okuthembekileyo, kunye nokusebenza okukhuselekileyo kombane wombane.
Inkcazo yedatha ye-CT Nameplate eqhelekileyo
I-CT Ratiyo (Eyokuqala / eSekondi yangoku)
Umzekelo: 1000/5 A
Intsingiselo: Xa i-1000 A ihamba kwiprayimari, i-5 A iya kufumaneka kwindawo yesibini.
Umthwalo (VA)
Umzekelo: 15 VA
Umthwalo ophezulu we-CT unokubonelela (iimitha + i-relay + ukumelana nekhebula).
Ukugqithiswa koku → ukuchaneka kuyehla.
Iklasi yokuchaneka
0.2 / 0.5 / 1 → Ukulinganisa i-CT (ukuchaneka okuphezulu, ukuhlawula, umlinganiselo).
5P / 10P / PS → Ukhuseleko lweCT (lusebenza ngokuchanekileyo ngexesha lemisinga yempazamo).
I-Voltage Point yedolo (Vk) (Ii-CTs zoKhuselo kuphela)
I-Voltge apho i-CT igcwele khona. Kubalulekile kukhuseleko olwahlukileyo.
I-ALF (I-Accuracy Limit Factor) (Ii-CTs zoKhuselo)
Umzekelo: ALF 10 → CT ihlala ichanekile ukuya kuthi ga kwi-10 × ireyithiwe yangoku.
ILF (Isixhobo soMda weFactor) (i-CTs yokulinganisa)
Umzekelo: ILF 5 → Ikhusela iimitha ukuba umsinga unyuka ngaphezu kwe-5 × ixabiso elilinganisiweyo.
Ikalwe ngokuqhubekayo (kwi)
I-CT inokuthwala le yangoku ngokuqhubekayo ngaphandle kokushisa.
Umzekelo: i-120% yereyithingi yangoku.
Ixesha elifutshane-Ixesha eliThermal langoku (Ith)
Impazamo ukumelana yangoku 1s okanye 3s.
Umzekelo: Ith=25 kA / 1s.
Dynamic yangoku (Idyn)
Ukumelana nomatshini ngexesha lesiphaluka esifutshane (ngokuqhelekileyo i-2.5 × Ith).
Ukuphindaphinda kunye noMgangatho
Umzekelo: 50 Hz, IEC 61869 / IS 2705.
Umzekelo CT Nameplate.
Umlinganiselo weCT: 1000/5 A
Umthwalo: 15 VA
Udidi oluchanekileyo: 0.5 (Ukulinganisa), 5P10 (uKhuselo)
Indawo yedolo: 100 V
ALF: 10
ILF: 5
Ukuba: 25 kA / 1s
Idyn: 62.5 kA
Ilinganiswe ngokuqhubekayo ngoku: 120%
Ukuphindaphinda: 50 Hz
Umgangatho: IEC 61869
Ukuqonda indlela yokufunda nokutolika i-nameplate ye-CT kubalulekile ekukhetheni imodeli ye-CT efanelekileyo, ukuqinisekisa umlinganiselo ochanekileyo wangoku, kunye nokugcina ukuthembeka kwenkqubo yombane. Ngokunikela ingqalelo kwiiparameters eziphambili ezifana nokulinganisa okuphambili kunye nesekondari, iklasi yokuchaneka, ukulinganiswa komthwalo, i-frequency, kunye neqondo lokushisa, unokwenza izigqibo ezinolwazi xa ukhetha kwaye ufaka ii-CTs kwizicelo zakho. Ukuba unemibuzo okanye iinkxalabo malunga nokufunda i-nameplate ye-CT, hlala ubonisana nomenzi okanye uchwepheshe oqeqeshiweyo wombane ukuze ufumane isikhokelo.