Umbuzo: Ukuba ubunyulu buhla ukuya kwi-95% ngenxa yokungena komoya, ngaba i-GIS isasebenza?
A: Iya kuhlala inamandla, kodwa imida yokhuseleko (i-arc quenching kunye nokupholisa) iyancipha ngokuyingozi.
Imingcipheko yokucoceka okuphantsi:
❶ Ukucima i-Arc eNcitshisiweyo: Umoya umbi nge-100x kune-SF6 kwindawo yokumisa ii-arcs. I-CB inokusilela ukuphazamisa.
❷ Ukutshatyalaliswa kobushushu: Ukungcola kutshintsha ukuxinana kwegesi kunye nokukwazi ukupholisa, okukhokelela ekugqithiseni.
Imigangatho (IEC 60480):
• Irhasi eNtsha: Inkulu kune okanye ilingana nama-99.9%.
• IGesi yokubaleka: Kufuneka ibe>> 97%. Ngaphantsi kwe-95% ifuna ukulungiswa kwakhona.
Sitolika njani amanqanaba e-SO2 kunye ne-HF?
Q: Umhlalutyi ubonisa i-5 ppm ye-SO2. Isiphumo esiqhelekileyo okanye impazamo yangaphakathi?
A: I-SO2 yi "Alarm yomsi" ye-arcing yangaphakathi. Tolika ngolu hlobo lulandelayo:
|
Inqanaba le-SO2 |
Ukutolikwa |
Isenzo |
|
< 1 ppm |
Ukusebenza okuqhelekileyo. |
Ukubeka iliso rhoqo. |
|
1 – 5 ppm |
I-PD encinci okanye ukutshintsha nzima. |
Lifutshane ixesha lovavanyo. |
|
5 - 10 ppm |
Kwenzeke isiphene esibalulekileyo. |
Phanda usebenzisa i-UHF/Acoustic PD. |
|
>10 ppm |
INGXAKI yomonakalo wangaphakathi. |
Ukuhlolwa / ukucocwa kwangoko. |
Ingcebiso yeNgcali: Ukuba zombini i-SO2 kunye ne-HF ziphezulu, unesiphene ESISEBENZAYO sivelisa iasidi ngoku.