Ukuba ubunyulu buhla ukuya kwi-95% ngenxa yokungena komoya, ngaba i-GIS isasebenza?

 Jun 30, 2026

 Shiya umyalezo

 

Umbuzo: Ukuba ubunyulu buhla ukuya kwi-95% ngenxa yokungena komoya, ngaba i-GIS isasebenza?

A: Iya kuhlala inamandla, kodwa imida yokhuseleko (i-arc quenching kunye nokupholisa) iyancipha ngokuyingozi.

Imingcipheko yokucoceka okuphantsi:

❶ Ukucima i-Arc eNcitshisiweyo: Umoya umbi nge-100x kune-SF6 kwindawo yokumisa ii-arcs. I-CB inokusilela ukuphazamisa.

❷ Ukutshatyalaliswa kobushushu: Ukungcola kutshintsha ukuxinana kwegesi kunye nokukwazi ukupholisa, okukhokelela ekugqithiseni.

Imigangatho (IEC 60480):

• Irhasi eNtsha: Inkulu kune okanye ilingana nama-99.9%.

• IGesi yokubaleka: Kufuneka ibe>> 97%. Ngaphantsi kwe-95% ifuna ukulungiswa kwakhona.

 

Sitolika njani amanqanaba e-SO2 kunye ne-HF?

Q: Umhlalutyi ubonisa i-5 ppm ye-SO2. Isiphumo esiqhelekileyo okanye impazamo yangaphakathi?

A: I-SO2 yi "Alarm yomsi" ye-arcing yangaphakathi. Tolika ngolu hlobo lulandelayo:

Inqanaba le-SO2

Ukutolikwa

Isenzo

< 1 ppm

Ukusebenza okuqhelekileyo.

Ukubeka iliso rhoqo.

1 – 5 ppm

I-PD encinci okanye ukutshintsha nzima.

Lifutshane ixesha lovavanyo.

5 - 10 ppm

Kwenzeke isiphene esibalulekileyo.

Phanda usebenzisa i-UHF/Acoustic PD.

>10 ppm

INGXAKI yomonakalo wangaphakathi.

Ukuhlolwa / ukucocwa kwangoko.

Ingcebiso yeNgcali: Ukuba zombini i-SO2 kunye ne-HF ziphezulu, unesiphene ESISEBENZAYO sivelisa iasidi ngoku.

Thumela u kuphanda
Thumela u kuphanda