Q: Ndiva malunga ne "Duval Triangle" kakhulu kwi-DGA yokutolika. Ingaba isebenza kanjani?
A: Unxantathu weDuval (nguMichel Duval, IREQ, ngoku IEEE C57.104) yeyona ndlela isetyenziswa kakhulu yegraphical yokuhlelwa kwempazamo yeDGA kusetyenziswa umzobo weternary.
Imiyinge emithathu yerhasi (unxantathu 1 - ioli yezimbiwa):
• %CH₄=CH₄ / (CH₄ + C₂H₄ + C₂H₂) × 100
• %C₂H₄=C₂H₄ / (CH₄ + C₂H₄ + C₂H₂) × 100
• %C₂H₂=C₂H₂ / (CH₄ + C₂H₄ + C₂H₂) × 100
|
Zowuni |
Uhlobo lwempazamo |
Inkcazo |
|
PD |
Ukukhupha inxalenye |
Aphantsi-icorona yamandla, entlantsila kwi-voids |
|
D1 |
Ukukhutshwa{0}} kwamandla aphantsi |
Intlantsi, ukulandelela (ukukhutshwa okukhanyayo) |
|
D2 |
Ukukhutshwa - kwamandla aphezulu |
I-Arcing ngamandla landela{0}} ngapha |
|
T1 |
Thermal <300 degree |
Ukufakwa ubushushu obugqithisileyo (ukujikajika okanye undoqo) |
|
T2 |
I-Thermal 300℃-700 degree |
Indawo eshushu, unxibelelwano lombane olubi |
|
T3 |
Thermal> 700 degree |
Indawo eshushu kakhulu, i-arcing enokwenzeka + thermal |
|
DT |
I-Mixed Thermal + Discharge |
Impazamo yokudibanisa |
Umzekelo wokuxilonga:
I-150 MVA isiguquli: CH₄=180 ppm, C₂H₄=280 ppm, C₂H₂=5 ppm
%CH₄=38.7%, %C₂H₄=60.2%, %C₂H₂=1.1%
→ Iwa kwindawo ye-T2 → i-thermal fault 300–700℃.
Iphezulu C₂H₄ + phantsi C₂H₂ → enokubakho umdibaniso ongalunganga okanye ucofe{1}}uqhagamshelwano lokutshintsha.
Isenzo: Jonga itephu{0}}abatshintshela abafowunelwa. Ukucima kweshedyuli ukuba i-C₂H₄ iyaqhubeka nokunyuka.
Ezinye iiDuval Triangles:
|
Unxantathu |
Isicelo |
Umahluko ongundoqo |
|
Unxantathu 1 |
Iziguquli zeoyile yezimbiwa (ezisemgangathweni) |
CH₄, C₂H₄, C₂H₂ |
|
Unxantathu 2 |
Ucokiso lwezowuni ye-Thermal fault |
CH₄, C₂H₄, C₂H₆ |
|
Unxantathu 3 |
{0}}iimpazamo zobushushu obuphantsi |
C₂H₄, C₂H₆, CH₄ |
|
Unxantathu 4 |
Layisha iTop Changer (LTCs) |
Iigesi ezifanayo, imida yendawo eyahlukileyo |
|
Unxantathu 5 |
I-ester yendalo (ioli yemifuno) |
Imida ehlengahlengisiweyo yeeoli ze-ester |
Imida:
• Ifuna ubuncinci iigesi zehydrocarbon ezintathu ezingaphaya kwemida yokubonwa.
• Ukuthembeka okunganeno xa irhasi enye> 80% yeHC iyonke.
• Ayikwazi ukwahlula iintlobo ezininzi zeempazamo ngaxeshanye.
• Soloko usetyenziswa ngamazinga okuvelisa igesi (ppm/ngosuku okanye ppm/ngenyanga).